Commutateur automatique intelligent à double alimentation

Commutateur automatique intelligent à double alimentation

TSMQ1 series intelligent self-protection double power automatic changeover switch (hereinafter referred to ATS) is suitable for rated working voltage AC440V, 50/60Hz, rated current 16A ~1250A.

Description

Application

This ATS is used as mutual conversion between normal power supply (N) and standby power supply (R) in emergency power supply system (can also be set manually) and also as a switch to control circuit with functions of controlling, signaling, interlocking, etc.

Some models of this series ATS are designed with communication port, which enables remote control; that is to say, it allows users to achieve unattended substation.

The ATS is suitable for residential areas, military facilities, hospitals, shopping malls, airports and other places.

Safety Precautions

1. Operate the device according to the manual.

2. Do not plug in or unplug the controller with power supply connected. That will cause electric shock or device damage.

3. Non professionals are not allowed to operate or repair the device.

4. Please refer to this manual to set the parameters of the controller.

5. The loading must be within the rated capacity, or it may cause release or burnt out.

6. Do not connect Neutral to any of the phase terminal. Phase number of the two circuits must be the same. When using 3 pole double power, please connect NN and RN to the pin NN and RN of terminal KG. Connect the ground wire properly.

7. Do not use the device outdoors.

8. Requirements for place for installation: no  flammable or explosive elements, no high humidity, no high temperature,

no vibration or shock, no conductive dust or elements.

9. Please follow requirements in this manual to ensure the lifetime.

Specification

Model Applicable Circuit Breaker Rated Working Current (A) Conversion Action Time (s) Utilization Category Mechanical Life (times) Electrical Life (times) Rated Short-circuit Impulse Withstand Voltage (Uimp) Rated Short-circuit Breaking Capacity Icu (kA)
TSMQ1-100 TSM2  series 100 ≤5 AC-33iB 5000 1000 8KV 10
TSMQ1-225 100,125,140, 160,180,200, 225 ≤5 5000 1000 10
TSMQ1-400 225,250,315, 350,400 ≤6 3000 1000 10
TSMQ1-630 400,500,630 ≤6 2500 500 12.6
TSMQ1-800 630,700,800 ≤6 2500 500 16
TSMQ1-1250 800,1000, 1250 ≤6 2500 500 25

Working Conditions 

  • Altitude: no more than 2000m for the installation site.
  • Ambient temperature: -5℃ ~ +40℃, and the average is no more than +35℃ within 24 hours.
  • Relative Humidity: no more than 50% RH at the highest temperature of +40℃; Higher relative humidity is allowable at lower temperature. Some measures should be taken for the condensation occasionally due to the temperature change.
  • Mounting conditions: ATS shall be mounted in the place that has no explosive medium, as well as no impact and vibration.

Product Dimension

TSMQ1 dimension

Model W(mm) L(mm) W1(mm) L1(mm) H(mm)
TSMQ1-100/3 390 220 350 185 118
TSMQ1-100/4 420 220 385 185 136
TSMQ1-225/3 430 220 395 195 139
TSMQ1-225/4 465 220 430 195 155
TSMQ1-400/3 565 310 51 285 190
TSMQ1-400/4 610 310 555 285 190
TSMQ1-630/3 630 320 575 295 195
TSMQ1-630/4 690 320 635 295 195
TSMQ1-800/3 705 340 655 315 190
TSMQ1-800/4 780 340 725 315 190
TSMQ1-1250/3 735 480 680 365 250
TSMQ1-1250/4 800 480 750 365 250